Firmware V3.15
21.04.2021
360/401
Menu1-6FrameHeater
MODE XXXXX
Frame Heater xxx Current ON/OFF status of frame heater output Terminal 91/92/93
Run Time xxx % Current on time of frame heater
Humidity xxx % Current ambient air humidity (transmitted via CAN bus from pack controller with fitted
ambient humidity sensor)
Room temp xx °C Current ambient air temperature (transmitted via CAN bus from pack controller with
fitted ambient temperature sensor
Menu1-7CoolingZone2
COOLING 2 XXXXX
Cooling XXX Current ON/OFF status of cooling
Run Time XX % Cooling relay on time during last day (00:00 - 24:00 hours)
Starts 0 Cooling relay actuations during last day
Temp. R4.3 XXX °C Current room air temperature Input Z71/Z72
Setpoint R4.3 XXX °C Room air temperature setpoint for comparison
Hystersis R4.3 XXX K Room air temperature hysteresis setpoint
Menu1-8DefrostZone2
DEFROST 2 Pos: XXXXX
Counting Rate Counting rate
Defrost Counter Defrost counter
Defrost Current ON/OFF status of defrosting
Temp. R1.3 XXX °C Current supply air temperature Input Z81/Z82
Temp. R1.4 XXX °C Current supply air temperature Input Z01/Z02
Def. End. Tmp. XXX °C Defrost termination temperature for comparison
Wait Time xx m Waiting time setpoint
Drip Time xx m Drain time setpoint
Last Defrst XX hh:mm Day and time of last defrost cycle started
Menu1-9FansZone2
FANS 2 Pos: XXXXX
FANS Fan ON/OFF
Temp. R1.3 Evaporator temperature Input Z81/Z82