Menu3-2-aDef.Tim.Z2
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Setting for how temperature zone 2 should
defrost:
With Z1 Together with zone 1
INT Internally
EXTExternally–thedefrostofboth
temperature zones is started
simultaneously via the external signal
, ,(ViaZ1,
ViaZ1,EXT,INT)
ViatZ1
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120 60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *)
, , (ON/OFF)
OFF
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day; shown only when parameter defrost
timer = INT
, , (Mo-Su) or numbers
(hh:mm)
Mo-Su
01:00
...
Defr. 14 xxxxx hh:mm
Menu3-3ToggleSetpoints
TOGGLE POS: XXXXX Entry Default
Status XXX Setpoint toggle status (OFF/ON) of alternative
set of setpoints (setpoint toggle)
Toggle Setp. XXX Setpoint toggle via
EXT digital input D21/22
INT internal timer
CANbus-„--"deactivated
Note: Care should be taken that the
corresponding digital input D21/D22 is set to
SOLLW.UMSCH (menu 6-2-4)
, , (EXT, INT, CAN, --)
EXT
Alt
ON: DD-DD hh:mm
Start time for toggle to alternative set of
setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3)
, , (Mo-Su etc.) or numbers
(hh:mm)
Mo-Su
21:00
Alt
OFF: DD-DD hh:mm
End time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3
, , (Mo-Su etc.) or numbers
(hh:mm)
Mo-Su
05:00
Alt
ON: DD-DD hh:mm
Start time for toggle to alternative set of
setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3)
, ,(Mo-Suetc.)ornumbers
(hh:mm)
Su
05:00
Alt
OFF: DD-DD hh:mm
End time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3
, ,(Mo-Suetc.)ornumbers
(hh:mm)
Su
21:00