If an alarm with a controller priority > 0 is pending and this priority is set to 0 before the alarm has
been marked as gone, the controller has no possibility to reset the alarm in the store computer.
Therefore, it is recommended after any change of alarm priorities to the value 0 to restart the
controller or ensure that the adjusted alarms are not active at the time of the adjustment.
If the case controller is used with store computers without extended priority allocation, the priorities
mayonlybeallocatedbetween0..2or"–"(seestorecomputeroperatingmanualforpriority
allocation). In the case of incorrect parametrisation, the alarm signalling behaviour of the store
computer is undefined (particularly with regard to the assignment of priorities to alarm destinations).
This also applies for the refrigeration point priority.