8.1.5 Parameter List S2: Setpoints Basic Parameters - Night Operation
CL1 CL2 Function/
Description
Range Default Dim. Displayed / Condition
NT LT HP
S210 S250 Second setpoint t
max
-50..45 -10 -38 25 °C Minimum of stage must be defined in CL:
CL1: S301 > 0 / CL2: S331 > 0
S211 S251 First setpoint t
min
-50..35 -16 -40 25
°C
(1), and temperature shift must be activated in CL:
CL1: S310 = 1 / CL2: S340 = 1
S212 S252 first setpoint
t-adjust.
_max
16..45 25 25 30
°C
S213 S253 first setpoint
t-adjust.
_min
0..20 15 15 0
°C
S214 S254 Neutral zone 2nd SP 1..10 4 4 6
K
Minimum of stage must be defined in CL:
CL1: S301 > 0 / CL2: S331 > 0
S215 S255 Control constant 2nd
SP
1..10 10 7 10
S216 S256 Activate humidity shift 0: nicht
aktiv
1: aktiv
0 0 0
-
(1), and humidity shift must be activated in CL:
CL1: S311 = 1 / CL2: S341 = 1
Parameter List S1 and S2: To change values set access level to setpoint adjustment enabled (Pa
rameter A060=1, see section 7.7 Changing the Access Level).