Parameter List and Menu Structure of VS 300
110
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
Parameter
No.
Alarm priorities for: Range Default
Displayed /
Condition
NT LT HP
S434
No UA300 available
(with control by refri
geration point activa
ted)
-: Not recorded
0: Only entered in report list
1: Alarm priority 1
2: Alarm priority 2
2 2 -
Al ways shown
S435
No load level informa
tion received CL1
(with to shift by refrige
ration point activated
in CL1)
2 2 -
S436
No load level informa
tion received CL2
(with to shift by refrige
ration point activated
in CL2)
2 2 -
Parameter List S4: To change values set access level to setpoint adjustment enabled
(Parameter A060=1, see section 7.7 Changing the Access Level).
8.1.12 Parameter List S5: Suction pressure shift / Additional Parameters
CL1 CL2 Function/
Description
Range
Dimension
Default Displayed / Condition
NT LT HP
S500 S550 Suction pressure
shift mode
CL1/CL2
0: No shift
1: Shift by refrige-
ration point
- 0 0 -
Minimum of one stage must be
defined in CL:
CL1: S301 > 0
CL2: S331 > 0
Control loop must be low-pres
sure loop (LT or NT)
S501 S551 Maximum load le
vel for t
o
shift
CL1/CL2
70..100 % 100 100 -
S502 S552 Minimum load le
vel for t
o
shift
CL1/CL2
10..60 % 50 50 -
S503 S553 Increment
CL1/CL2
0,0..10,0 K 1,0 1,0 -
S504 S554 Time interval t
o
shift CL1/CL2
1..20 min 5 5 -
Parameter List S3: To change values set access level to setpoint adjustment enabled
(Parameter A060=1, see section 7.7 Changing the Access Level).