Parameter List and Menu Structure of VS 300
109
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
Controller configuration must be made prior to making individual parameter settings, as first start is
performed after changing configuration!
In first start, default settings are loaded for all parameters and all archives (alarms and operating
data, e.g. run times, starts, activity) are deleted!
8.1.11 Parameter List S4: Setpoints Alarm Priorities
Parameter
No.
Alarm priorities for: Range Default
Displayed /
Condition
NT LT HP
S400 High pressure CL1
-: Not recorded
0: Only entered in report list
1: Alarm priority 1
2: Alarm priority 2
2 2 2
Always shown
S401 High pressure CL2
2 2 2
S402 Low pressure CL1
2 2 2
S403 Low pressure CL2
2 2 2
S404 Pressure measuring
loop error CL1
2 2 2
S405 Pressure measuring
loop error CL2
2 2 2
S409 Service mode active
0 0 0
S410 Load shedding activa
ted
0 0 0
S411 Fast unload activated
0 0 0
S416 Setpoint changed
0 0 0
S417 Controller configura
tion changed LT, NT,
HP
0 0 0
S418
External alarm via di
gital inputs 1 - 4
2 2 2
S419
S420
S421
S422
Sensor type changed 2 2 2
S430
Power failure/restart 0 0 0
S431
First start 2 2 2
S432
Low battery 2 2 2
S433
Internal error 2 2 2