Parameter List and Menu Structure of VS 300
121
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
S Menu 2-1 Analog values
ANALOV. POS: XXXXX
Act.px CL1 +/-/= X.XX bar Current evaporating/condensing pressure Control Loop 1
Setp.px CL1 D/N/HR X.XX bar Target evaporating/condensing pressure Control Loop 1 for comparison
Act.tx CL1 +/-/= X.XX °C Current evaporating/condensing temperature Control Loop 1
Setp.tx CL1 D/N/HR X.XX °C Target evaporating/condensing temperature Control Loop 1 for comparison
tuIst RK1 XX °C Current room/outside temperature Control Loop 1
(only shown when activated)
Feuchte RK1 Current air humidity Control Loop 1 (only shown when activated)
AnalogOut RK1 XXX % Current controller output at analog output for Control Loop 1
(only shown when speed control or combined control is activated)
Act.px CL2 +/-/= X.XX bar Current evaporating/condensing pressure Control Loop 2
Setp.px CL2 D/N/HR X.XX bar Target evaporating/condensing pressure Control Loop 2 for comparison
Act.tx CL2 +/-/= X.XX °C Current evaporating/condensing temperature Control Loop 2
Setp.tx CL2 D/N/HR X.XX °C Target evaporating/condensing temperature Control Loop 2 for comparison
tuIst RK2 XX °C Current room/outside temperature Control Loop 1
(only shown when activated)
Feuchte RK2 Current air humidity Control Loop 2 (only shown when activated)
AnalogOut CL2 XXX % Current controller output at analog output for Control Loop 2
(only shown when speed control or combined control is activated)
N Night operation
px P
0
or P
c
D Day operation
tx t
0
or t
c
HR Heat recovery mode
+ Temperature high, above neutral zone
- Temperature low, below neutral zone
= Temperature within neutral zone
S Menu 2-2 Compressor/Fan Control Loop 1
CL1-COMP./COND POS: XXXXX
Stage 1 XXX Display ON/OFF: Actuating status of digital output, relay/control stage 1
... Only actual number of compressor/fans in Control Loop 1 is shown
Stage 12 XXX Display ON/OFF: Actuating status of digital output, relay/control stage 12
1)
1)
Number of relay/control stages CL1 [1..n] + Number of relays CL2 [n+1..m] + Number internal alarm relay
<= Number of relay/control stages VS 300 (max. 4/8/12 depending on expansion stage and configuration),
see section 4.1.1 System Configuration - Allocation of Relay/Control Stages