System integration Proline Prosonic Flow P 500 HART
92 Endress+Hauser
Parameter Description Selection / User entry Factory setting
Burst variable 0 For HART command 9 and 33: select the
HART device variable or the process variable.
• Not used
• Volume flow
• Mass flow
• Flow velocity
• Sound velocity
• Temperature
*
• Pressure
*
• Density
*
• Reference density
*
• S&W volume flow
*
• GSV flow
*
• NSV flow
*
• API gravity
*
• API slope
*
• Electronics temperature
• Signal strength
*
• Signal to noise ratio
*
• Acceptance rate
*
• Turbulence
*
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Cross flow factor
*
• Profile factor
*
• Primary variable (PV)
• Secondary variable (SV)
• Tertiary variable (TV)
• Quaternary variable (QV)
• HART input
• Percent of range
• Measured current
• Current input 1
*
• Current input 2
*
• Current input 3
*
Volume flow
Burst variable 1 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 2 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 3 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 4 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 5 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 6 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 7 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst trigger mode Select the event that triggers burst message
X.
• Continuous
• Window
• Rising
• Falling
• On change
Continuous
Burst trigger level Enter the burst trigger value.
Together with the option selected in the
Burst trigger mode parameter the burst
trigger value determines the time of burst
message X.
Signed floating-point number –