When Power Distribution Units (2U) Are Installed
The following procedure explains how to connect the power cords when a 2U power distribution unit (16 outlet
type) is installed.
1 Remove the cable holders from the power distribution unit.
Loosen the eight M3 screws on both sides of the cable holder to remove it.
M3 screw
Cable holder
M3 screw
2 Connect the power distribution unit outlets and power supply unit inlets with the power cords (AC output
cables).
The procedure to connect the power supply unit is same as Step 1 in "When No Power Distribution Units
Are Installed" (page 58).
IMPORTANT
โ€ข Connect the PSU#0 power cord to power distribution unit#0 (the lower power distribution unit).
Connect the PSU#1 power cord to power distribution unit#1 (the higher power distribution unit).
โ€ข For the high-density drive enclosure, connect the PSU#0 and PSU#2 power cords to power
distribution unit#0 (the lower power distribution unit). Connect the PSU#1 and PSU#3 power
cords to power distribution unit#1 (the higher power distribution unit).
4. Connecting Cables
Power Cord Connection
61 Configuration Guide (Basic)