Installing Power Distribution Unit (2U)
This section describes how to install a 2U power distribution unit in a rack.
1 Attach the M5 cage nuts to the rear rack pillar.
โข Attachment positions
On either side, insert eight M5 cage nuts in the 1st, 3rd, 4th, and 6th holes above the power
distribution unit base line.
1U
1U
2U
Power distribution unit
Power distribution unit
(Rack pillar: rear)
Power distribution unit
base line
M5 cage nut M5 cage nut
1st hole
3rd hole
4th hole
6th hole
1st hole
3rd hole
4th hole
6th hole
[Left] [Right]
โข Attachment procedure
Clip the M5 cage nut tabs into the desired hole from the inside.
Side view
M5 cage nut
Rack pillar (square hole)
2 Attach the cable holders to the power distribution unit.
Use eight M3 screws to attach the cable holders.
M3 screw
Cable holder
M3 screw
3. Rack Installation
Power Distribution Unit Installation
32 Configuration Guide (Basic)