Concord 4
Installation Manual
4
numbers 60-746-01, 60-803, 60-804, 60-820, 60-983, 60-984, 60-985, and 600-1020. UL requirements take
priority over SIA requirements.
SIA setting requirements
Table 1 describes programming requirements to meet ANSI-SIA CP-01.
Table 2 describes nonprogrammable (hard coded) system operation as required to meet ANSI-SIA CP-01 and
is provided only for your reference.
Note: You may use the silent arming feature to suppress arming level and exit beeps for the current arming period. Refer to
the Concord 4 User Manual (466-2183) for more information on silent arming.
Table 1. SIA setting requirements
Shortcut # Function
Programming
page reference
Testing page
reference Default setting Required setting
0013 - 0063 Exit extension 29 70 On On
0016 - 0066 Duress code 30 70 Disabled Disabled
02006 Dialer abort delay 35 70 30 Sec. 15 to 45 sec.
02007 Cancel message 36 70 On On
02009 Call wait cancel 36 70 Disabled On if reporting to central
station and customer has call
waiting service
0310 - 0360 Entry delay 40 70 30 sec. 30 to 240 sec.
0311 - 0361 Exit delay 40 70 60 sec. 45 to 184 sec.
06015 Swinger limit 46 70 1 1
1100 Smoke verify 58 70 Off On if smoke alarms are
programmed into system
N/A Cross-zoning 91 70 Disabled Enabled for zones with a high
probability of false alarms
Table 2. ANSI-SIA CP-01 requirements
Function Operation
SIA false alarm Enabled
Auto stay arming Enabled
Disarm during entry delay Enter code only (or 1 + CODE)
Cancel alarm Enter code only (or 1 + CODE)
Abort annunciation Enabled
Entry/exit progress annunciation Enabled