Concord 4
Installation Manual
6
UL 1635 digital alarm communicator system
For UL 1635 installations, entry delay plus dialer abort delay must not exceed 60 seconds. Same as UL 1023,
985, and 1610 plus:
AC failure set to on
Phone number must be programmed
Low CPU battery set to on
Next phone test set to 1
Phone test frequency set to 1
High level reports set to on
Low level reports set to on
Communication failure set to on
RF Tx timeout set to 4 hours
Central station reporting
The panel was tested with the following central station receivers using SIA and contact ID reporting formats:
CS-5000 central station receiver
Sur-Gard central station receiver with models SG-DRL2A and SG-CPM2
Osborne Hoffman central station receiver
Note: The installer must verify the compatibility between this panel and the central station receivers being used.
UL Canada listed installations
This section describes the requirements for CUL (UL Canada) listed installations.
Residential burglary alarm system unit (ULC subject C1023-1974)
Basic system as described for UL 1023 listed installations plus:
Hardwire magnetic contact (13-068 or 13-071) or wireless learn mode door/window sensor (60-362)
Siren timeout set to 5 minutes or more
Residential fire warning system control unit (ULC-S545-M89)
Basic system as described for UL 985 Listed Installations plus:
Hardwired smoke detector: System sensor models 2400 or 2400TH learned into sensor group 26, or
ESL models 429AT, 429C, 429CT, 521B, 521BXT, 521NCSXT, 711U, 711UT, 721U, 721UT, TS7-2,
or TS7-2T learned into sensor group 26.
Wireless smoke sensor 60-506-319.5 or 60-848-02-95 learned into sensor group 26.
Immediate trouble beeps set to on.
Note: For 24-hour backup, external power drain is limited to 90 mA (during normal standby condition) using a 4.5 or 5.0 Ah
battery, or 190 mA continuous using a 7.0 Ah battery.
RF Tx timeout set to 4 hours (if system includes SuperBus 2000 RF transceiver and wireless smoke
sensors).
Siren timeout set to 5 minutes or more.

Table of Contents

Other manuals for GE Security Concord 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Concord 4 and is the answer not in the manual?

GE Security Concord 4 Specifications

General IconGeneral
BrandGE Security
ModelConcord 4
CategorySecurity System
LanguageEnglish

Related product manuals