173
Notes for response numbers
The mechanical lifetime of the relay may be exceeded if an output is set up for a siren tracking response and a
pulsing siren (auxiliary or fire) is active for long time periods. A SnapCard relay output’s lifetime expectancy
is about 350 total pulsing hours.
• If an event does not trigger sirens, siren tracking response numbers activate without turning on the
output. If sirens are triggered by another event, the output pulses to match the siren. If the siren
cadence changes (from police to fire, for example), outputs set up for siren tracking change to match
the siren and all pulsing outputs pulse to one common cadence.
• If an event does not trigger sirens, siren time response times activate outputs only if sirens are active
for another reason.
• If an alarm event does not necessarily require disarming (no activity, closing report, etc.), outputs set
up for a sustained response time remain activated until the next arming level change.
• If an event occurs that activates an output set up for trip delay, the delay and output activation can be
canceled by trigger event restoral.
Note: The trip delay is factory set for 30 seconds and cannot be changed.
Activated outputs set up for a 3-minute response time remain active for the entire three minutes. To deactivate the output before the 3-
minute time expires, you must enter program mode or remove panel power. Activated outputs set up for a momentary or 3-minute re-
sponse time restart if the same trigger event occurs again.
Table 32. Response numbers
Siren tracking Trip delay Response time Response no.
no no momentary 00
no no 3 minutes
5
01
no no siren time
2
02
no no sustained
3
03
no yes
4
momentary 04
no yes
4
3 minutes
5
05
no yes
4
siren time
2
06
no yes
4
sustained
3
07
yes
1
no momentary 08
yes
1
no 3 minutes
5
09
yes
1
no siren time
2
10
yes
1
no sustained
3
11
yes
1
yes
4
momentary 12
yes
1
yes
4
3 minutes
5
13
yes
1
yes
4
siren time
2
14
yes
1
yes
4
sustained
3
15