Security applications
2.10 EST3 Installation and Service Manual
The CMS must have a maximum response time of 30 minutes.
When this application includes partitions, the partition that
contains the EST3 panel equipped with the 3-MODCOM and
local bell must be armed 24 hours a day, and have limited, high-
level access.
Police station connect certificate
The equipment, installation requirements, and application
restrictions for a Police Station Connect Certificate installation
are the same as for a Central Station Alarm Certificate
installation, as described above.
Central station alarm certificate
Figure 2-3 shows the equipment that can be used as part of a
Central Station Alarm Certificate installation.
ATCK Attack Kit
Central
monitoring
station
Control Panel
Power supply
Other factors
Hardware configuration
SDU programming
ACDB/KDC operation
X
3-SAC
3-MODCOM
3-TAMPRCC Cabinet
Tamper Switch
SAC bus
KPDISP
Telephone lines: one
line with 24-hour test or
two lines with line cut
monitors
Figure 2-3: Central station certificate
This certificate requires that the control panel be fitted with an
ATCK Attack Kit and a 3-TAMPRCC Cabinet Tamper Switch.
No local bell is required.
A single phone line that is tested at least once in every 24-hour
period can be used. Alternately, two lines with line cut
monitoring can be used in place of a line with 24-hour testing.