Chapter 2: Front panel programming 
106  Vigilant VS1 and VS2 Technical Reference Manual 
Option Description 
Acct 1 2: Event information is sent to both dialer accounts 
Acct 1: Event information is sent to dialer account one 
Acct 2: Event information is sent to dialer account two 
None: Event information is not sent to the dialer 
NET: Yes or No. Controls whether event information is sent to the 
connected network 
CID: Contact ID event code (000 to 999) 
 
To program a NAC: 
1.  Display the panel configuration options menu. See 
“Panel programming” on page 103. 
2.  Choose Panel NAC. 
3.  Enter the NAC (number) you want to program. 
Note: NAC 3 and 4 are not available if either NAC 1 or
2 or both are set to Class A. 
4.  Program each NAC in the system using Table 27 on 
page 104. 
5.  When you finish programming each option, choose 
Save. 
6.  Press the Menu button to exit menu mode, or 
continue programming. 
 
 
Panel Configuration 
Panel NAC 
Ann. Class  A<>
Annunciator 
⇩ 
Panel NAC 
NAC 1<>
 
⇩ 
Panel NAC  1
Class A<>
Type Cont. Non 
Sil<> 
Label > 
⇩ 
Panel NAC  1
Correlation Groups 
Event Notification 
Save 
Setting annunciator classes 
The annunciators connected to the system must have their wiring class (Class A or 
Class B) programmed. 
Default: Class B 
To set the annunciator class: 
1.  Display the panel configuration options menu. See 
“Panel programming” on page 103. 
2. Choose Ann. Class. 
3.  Select either Class A or Class B. 
4.  Program other panel configuration options or choose
Save if you’re finished. 
 
 
Panel Configuration 
Panel NAC 
Ann. Class  A<>
Annunciator 
⇩   
Panel Configuration 
Ann. Class  A<>
Annunciator