Chapter 2: Front panel programming
106 Vigilant VS1 and VS2 Technical Reference Manual
Option Description
Acct 1 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET: Yes or No. Controls whether event information is sent to the
connected network
CID: Contact ID event code (000 to 999)
To program a NAC:
1. Display the panel configuration options menu. See
“Panel programming” on page 103.
2. Choose Panel NAC.
3. Enter the NAC (number) you want to program.
Note: NAC 3 and 4 are not available if either NAC 1 or
2 or both are set to Class A.
4. Program each NAC in the system using Table 27 on
page 104.
5. When you finish programming each option, choose
Save.
6. Press the Menu button to exit menu mode, or
continue programming.
Panel Configuration
Panel NAC
Ann. Class A<>
Annunciator
⇩
Panel NAC
NAC 1<>
⇩
Panel NAC 1
Class A<>
Type Cont. Non
Sil<>
Label >
⇩
Panel NAC 1
Correlation Groups
Event Notification
Save
Setting annunciator classes
The annunciators connected to the system must have their wiring class (Class A or
Class B) programmed.
Default: Class B
To set the annunciator class:
1. Display the panel configuration options menu. See
“Panel programming” on page 103.
2. Choose Ann. Class.
3. Select either Class A or Class B.
4. Program other panel configuration options or choose
Save if you’re finished.
Panel Configuration
Panel NAC
Ann. Class A<>
Annunciator
⇩
Panel Configuration
Ann. Class A<>
Annunciator