Simon Security System
2
• Option 29: Control Panel Alarms set to on
• Option 39: Siren Timeout set to 4 minutes or more
• Option 40: Trouble Beeps set to on
• Option 50: RF Jam Detect set to on
• Option 53: Hardwire Siren Supervision set to on if Option 29: Control Panel 
Alarms is set to off
• Option 85: Smoke Supervision must be set to on
UL 1023 & 985 24-Hour Backup
• For 24-hour backup, the total current draw for all connected devices is limited to 25 
mA (during normal standby conditions) using a 1.2 AH battery.
UL 1635 Digital Alarm Communicator System
Same as UL 1023 & 985, plus:
Note  
These option settings are in 
addition to UL 1023 and 985 
and are required only if the 
system is set up for Central 
station reporting.
• Option 12: Phone 1 Reports set to 0 or 1
• Option 16: Auto Phone Test set to 001
• Option 19: RF Timeout set to less than 4 hours
• Option 24: AC Power Failure Report set to on
• Option 25: CPU Low Battery Report set to on
• Option 26: Fail to Communicate set to on
• Option 50: RF Jam Detect set to on
• Option 10 and 17: Entry Delay plus the Dialer Delay must not exceed 60 seconds
SIA System Requirements
Note  
UL requirements take prior-
ity over SIA requirements.
SIA system requirements are the same as those described for a UL Listed Basic System 
on page 1, plus:
• If multiple annunciation is required, use Hardwire Siren part no.13-046.
SIA Setting Requirements
The following table describes programming requirements to meet ANSI-SIA CP-01.
Opt. 
#
Function Programming 
Page Reference
Testing Page 
Reference
Default 
Setting
Required Setting
10 Entry Delay 26 58 30 sec. 30-254 sec.
11 Exit Delay 27 58 60 sec. 45-254 sec.
17 Dialer Delay 29 58 30 sec.  15-45 sec.
38 Auto Arm 37 58 On On
45 Sensor Alarm 
Restoral Report
40 58 Off 3
52 Unvacated 
Premises
42 58 On On
56 Call Waiting 44 58 Off On if reporting to central 
station and customer has call 
waiting service
59 Exit Extension 45 58 On On
68 Swinger Shutdown 48 58 On (one 
trip)
On (one trip)
69 SIA Limits 48 58 On On
86 Fire Alarm Verify 54 58 Off On