Simon Security System
2
Option 29: Control Panel Alarms set to on
Option 39: Siren Timeout set to 4 minutes or more
Option 40: Trouble Beeps set to on
Option 50: RF Jam Detect set to on
Option 53: Hardwire Siren Supervision set to on if Option 29: Control Panel
Alarms is set to off
Option 85: Smoke Supervision must be set to on
UL 1023 & 985 24-Hour Backup
For 24-hour backup, the total current draw for all connected devices is limited to 25
mA (during normal standby conditions) using a 1.2 AH battery.
UL 1635 Digital Alarm Communicator System
Same as UL 1023 & 985, plus:
Note
These option settings are in
addition to UL 1023 and 985
and are required only if the
system is set up for Central
station reporting.
Option 12: Phone 1 Reports set to 0 or 1
Option 16: Auto Phone Test set to 001
Option 19: RF Timeout set to less than 4 hours
Option 24: AC Power Failure Report set to on
Option 25: CPU Low Battery Report set to on
Option 26: Fail to Communicate set to on
Option 50: RF Jam Detect set to on
Option 10 and 17: Entry Delay plus the Dialer Delay must not exceed 60 seconds
SIA System Requirements
Note
UL requirements take prior-
ity over SIA requirements.
SIA system requirements are the same as those described for a UL Listed Basic System
on page 1, plus:
If multiple annunciation is required, use Hardwire Siren part no.13-046.
SIA Setting Requirements
The following table describes programming requirements to meet ANSI-SIA CP-01.
Opt.
#
Function Programming
Page Reference
Testing Page
Reference
Default
Setting
Required Setting
10 Entry Delay 26 58 30 sec. 30-254 sec.
11 Exit Delay 27 58 60 sec. 45-254 sec.
17 Dialer Delay 29 58 30 sec. 15-45 sec.
38 Auto Arm 37 58 On On
45 Sensor Alarm
Restoral Report
40 58 Off 3
52 Unvacated
Premises
42 58 On On
56 Call Waiting 44 58 Off On if reporting to central
station and customer has call
waiting service
59 Exit Extension 45 58 On On
68 Swinger Shutdown 48 58 On (one
trip)
On (one trip)
69 SIA Limits 48 58 On On
86 Fire Alarm Verify 54 58 Off On