EasyManuals Logo

Hakko Electronics V Series User Manual

Hakko Electronics V Series
332 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #175 background imageLoading...
Page #175 background image
32-2 32. Yaskawa Electric PLC
CP9200SH/MP900
Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the
range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro
programs.
Memobus
CP9200SH/MP900
When setting the MB/IB memory, set the bit numbers in the
hexadecimal notation.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Port 1 1
Parity Even Even
Transmission
code
Data length 8 8
Stop bit 1 1
Error check CRC (fixed) −
Port delay timer 0 (fixed) −
Memory TYPE Remarks
4 (word device) 0
3 (input register) 1 Including constant register, read only
R (link register) 2
A (extension register) 3
0 (coil) 4
D (link coil) 5
1 (input relay) 6 Read only
7 (constant register) 7
Memory TYPE Remarks
MW (holding register) 0
IW (input register) 1 Read only
MB (coil) 4
IB (input relay) 6 Read only
MBxxxx
DEC
Bit No.: HEX

Table of Contents