CAUTION:CAUTION: To maintain proper system cooling, do not operate the server for long period with the access panel open or
removed. Operating the server in this manner results in an improper system airflow. For internal hot-plug component
procedures, complete the procedure within 60 seconds. Failure to do so can cause the system temperature to increase and
trip the safety threshold. When this happens:
The health LED flashes amber.
The operating system gracefully shuts down.
CAUTION:CAUTION: To prevent improper cooling and thermal damage, do not operate the server unless all bays are populated with
either a component or a blank.
IMPORTANT:IMPORTANT:
The fan setup can either be standard, single-rotor fans or high-performance, dual-rotor fans. Do not mix fan types in the
same server.
ProcedureProcedure
1. If installed, open the cable management arm.
2. Extend the server from the rack .
3. Remove the access panel.
4. Remove the fan:
a. Press and hold the latch (callout 1).
b. Lift the fan from the fan cage (callout 2).
HPE ProLiant DL385 Gen11 Server Maintenance and Service Guide 96