Congurable Parameters
Parameter Name Description
Battery unit Displays or sets the battery model. The system
automatically identies and displays the
correct model. Generally, you do not need to
manually modify the information.
Maximum charge power Sets the maximum power for battery charging.
Maximum discharge power Sets the maximum power for battery
discharging.
Charge from AC If this parameter is set to Enable, the batteries
can be charged from the power grid.
Maximum charge power of
grid
Sets the maximum power for charging the
batteries from the power grid.
Charge cuto capacity When the SOC of the battery reaches this
value, charging stops.
Max. depth of discharge When the SOC of the battery reaches this
value, discharging stops.
Grid charge cuto SOC When the SOC of the battery reaches this
value, the grid stops charging the battery.
Charge/Discharge
Parameter Name
Description
Charge/Discharge Forcible battery charge and discharge
operation, which can be Charge, Discharge, or
Stop.
Charge setting mode To enter the forced charge/discharge mode, set
Duration or Target SOC.
Duration Sets the duration of forced charge and
discharge. When it reaches the time, the forced
charge and discharge stops automatically. It is
displayed when Charge setting mode is set to
Duration.
Charged energy Sets the Target SOC for forced charge and
discharge. When the SOC reaches this value,
the forced charge and discharge stops
automatically. It is displayed when Charge
setting mode is set to Target SOC.
Discharged energy Current charged energy in the forced charge/
discharge mode
SmartLogger3000
User Manual 6 WebUI Operations
Issue 10 (2022-08-20) Copyright © Huawei Technologies Co., Ltd. 144