Parameter Description
Read mode The value can be Multiple read or Single read.
Start address If Read mode is set to Multiple read, set the start
address for reading.
End address If Read mode is set to Multiple read, set the end
address for reading.
Signal parameters
NOTE
Signal parameters
include Signal Name,
Signal address, Gain,
Oset, and Unit.
Set these parameters based on the vendor protocol.
NOTE
If the EMI can collect a signal, set Signal address for the
signal to the corresponding register address. If the EMI
cannot collect a signal, set Signal address for the signal to
65535.
----End
6.3.17.2 Setting AI EMI Parameters
Procedure
Step 1 Set access parameters and click Add Devices.
Figure 6-55 Setting access parameters
Parameter
Description
Device Type Set this parameter to EMI.
Connection mode Set this parameter to AI.
Address Set this parameter to the
communication address of the EMI.
Step 2 Choose Monitoring > EMI > Running Param., set running parameters and click
Submit.
SmartLogger3000
User Manual 6 WebUI Operations
Issue 10 (2022-08-20) Copyright © Huawei Technologies Co., Ltd. 178

Table of Contents

Other manuals for Huawei SmartLogger3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SmartLogger3000 and is the answer not in the manual?

Huawei SmartLogger3000 Specifications

General IconGeneral
BrandHuawei
ModelSmartLogger3000
CategoryData Loggers
LanguageEnglish

Related product manuals