9 Technical Specications
9.1 Technical Specications of the SmartLogger
Device Management
Parameter Specications
Number of solar inverters ● SmartLogger3000A: can connect to a
maximum of 80 solar inverters.
● SmartLogger3000B: can connect to a
maximum of 150 solar inverters.
Communications mode RS485, ETH, MBUS (optional), 4G
(optional), and SFP (optional)
Maximum communication
distance
● RS485: 1000 m
● ETH: 100 m
● MBUS (multi-core cable): 1000 m;
MBUS (single-core cable): 400 m (The
three-phase cables must be bound at 1
m intervals)
● Optical ber (single-mode, 1310 nm
optical module): 10,000 m (with the
1000M optical module); 12,000 m (with
the 100M optical module)
SmartLogger3000
User Manual 9 Technical Specications