Parameter Description
Time for
communication
exception detection (s)
The default value is 300. This parameter is used only
for shutdown protection when the communication
between the SmartLogger and the scheduling backend
is abnormal. If the communication is interrupted for a
period longer than the set value, it is determined as
abnormal.
Automatic startup
upon communication
recovery
The default value is Enable. If this parameter is set to
Enable, allows a device to be automatically started if
the communication recovers after an exception.
Limit solar inverter
power upon active
power scheduling
timeout
The default value is Disable. If this parameter is set to
Enable, the SmartLogger controls the device in the
following ways after the communication between the
SmartLogger and the scheduling backend is
interrupted for a period longer than the set value of
Active power scheduling timeout threshold for
triggering solar inverter power limiting.
Limit the active power of the inverter based on the
value of Power (in percentage of rated power) of
solar inverter in case of active power scheduling
timeout.
Limit the active power of the PCS based on the
value of Power (in percentage of rated power) of
ESS in case of active power scheduling timeout.
Active power
scheduling timeout
threshold for triggering
solar inverter power
limiting (s)
The default value is 300.0. This parameter is used only
for active power limiting protection when the
communication between the SmartLogger and the
scheduling backend is abnormal. If the
communication is interrupted for a period longer than
the set value, active power limiting protection is
started.
Power (in percentage
of rated power) of
solar inverter in case of
active power
scheduling timeout (%)
The default value is 0.0. After Limit solar inverter
power upon active power scheduling timeout is
enabled, if the communication between the
SmartLogger and the scheduling backend is
interrupted for a period longer than the set value of
Active power scheduling timeout threshold for
triggering solar inverter power limiting, the
SmartLogger limits the active power of the inverter
based on the set value of this parameter.
SmartLogger3000
User Manual 6 WebUI Operations
Issue 10 (2022-08-20) Copyright © Huawei Technologies Co., Ltd. 204

Table of Contents

Other manuals for Huawei SmartLogger3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SmartLogger3000 and is the answer not in the manual?

Huawei SmartLogger3000 Specifications

General IconGeneral
BrandHuawei
ModelSmartLogger3000
CategoryData Loggers
LanguageEnglish

Related product manuals