Table 6-9 DRM requirements
Mode Corresponding
Port on the
SmartLogger
Requirements Remarks
DRM0 AI2–AI4 ● When S0 is turned on, the
inverters shut down.
● When S0 is turned o, the
inverters are connected to the
power grid.
N/A
DRM5 DI1 When S5 is turned on, the
inverters do not output active
power.
When two or
more DRM
modes are
used at the
same time,
the strictest
requirement
must be met.
DRM6 DI2 When S6 is turned on, the
output active power of the
inverters does not exceed 50%
of the rated power.
DRM7 DI3 When S7 is turned on, the
output active power of the
inverters does not exceed 75%
of the rated power, and the
inverters consume the maximum
reactive power.
DRM8 DI4 When S8 is turned on, the
output active power of inverters
recovers.
NOTE
The inverters output active power
based on the percentage set on the
SmartLogger.
Procedure
Step 1 Click Settings and ensure that Active Power Control Mode is set to No limit,
Reactive Power Control Mode is set to No output, and connection port for
Remote Shutdown is set to No.
Step 2 Set DRM parameters and click Submit.
Figure 6-80 Setting DRM parameters
SmartLogger3000
User Manual 6 WebUI Operations
Issue 10 (2022-08-20) Copyright © Huawei Technologies Co., Ltd. 225