Alarm
ID
Alarm Name Alarm
Severity
Alarm
Sub-ID
Cause Suggestions
1106 AC SPD Fault Major 1 The SPD in
the smart
array
controller is
faulty.
● Check whether the cable to
the SPD in the smart array
controller is loose,
disconnected, or reversely
connected. If so, reconnect
the cable
rmly.
● Check whether the SPD in the
smart array controller is
faulty. If so, replace the faulty
SPD.
1107–
1110
DI1 user-
dened alarm
to DI4 user-
dened alarm
Major 1 The dry
contact signal
from the
peripheral to
the
corresponding
DI port of the
SmartLogger
is abnormal.
● Check the DI port cable
connection. If the cable is
loose, disconnected, or
reversely connected,
reconnect it rmly.
● Check that the relevant device
works properly.
1111–
1114
M1.DI1 user-
dened alarm
to M1.DI4
user-dened
alarm
Major 1 The dry
contact signal
from the
peripheral to
the
corresponding
DI port of the
SmartModule
is abnormal.
● Check the DI port cable
connection. If the cable is
loose, disconnected, or
reversely connected,
reconnect it rmly.
● Check that the relevant device
works properly.
1115 24 V Power
Failure
Major 1 The 24 V
power supply
in the smart
array
controller is
faulty.
1. Check whether the cable to
the 24 V power supply in the
smart array controller is
loose, disconnected, and
connected in reverse. If so,
reconnect the cable securely.
2. Check whether the 24 V
power supply in the smart
array controller is faulty.
Replace the faulty power
module.
1116 WebUI Server
Certicate
Invalid
Warning 1 WebUI Server
Digital
Signature
Certicate
Invalid
Check the time or change the
digital signature certicate.
SmartLogger3000
User Manual 7 Device Maintenance
Issue 10 (2022-08-20) Copyright © Huawei Technologies Co., Ltd. 236