Capacity 3000 W (maximum 3000 W)
PSM 1
Input 1 232 419
Output 11.99 334.33
Capacity 3000 W (maximum 3000 W)
Item Used(W)
Routing Engine 0 26
CB 0 5
System:
Zone 0:
Capacity: 6000 W (maximum 6000 W)
Actual usage: 1023 W
Total system capacity: 6000 W (maximum 6000 W)
PTX10001-36MR AC/HVDC Power Specicaons
The PTX10001-36MR operates within the AC/HVDC input voltage range listed in Table 12 on page
30. The PTX10001-36MR power consumpon is listed in Table 13 on page 30.
Table 12: PTX10001-36MR AC/HVDC Power
Specicaons
Parameter Minimum Rated Maximum
Input voltage (AC) 180 VAC 200-277 VAC 305 VAC
Input voltage (HVDC) 204 VDC 240-380 VDC 400 VDC
AC input line frequency 47 Hz 50-60 Hz 63 Hz
Table 13: PTX10001-36MR AC/HVDC Power Consumpon
Item Specicaon
Typical power consumpon 1538 W
Maximum power consumpon 2164 W