Table 33: Alarms for Services Gateway Chassis Components (continued)
Alarm SeverityActionAlarm ConditionsComponent
Steady red (major)Replace the power supply.A power supply has failed.Power supply
Install a power supply unit in the
empty slot. The services gateway
requires two power supply units
to be installed.
A power supply unit is not
present.
Verify and ensure that the power
cord is connected properly.
Power cord is not
connected.
Yellow (minor)As it is a non-recoverable fault,
replace the power supply.
Power supply fan failure.
Red (major)
•
Check the voltage of the
power source if it is in the
operating range.
•
Open a support case using the
Case Manager link at
https://www.juniper.net/support/
or call 1-888-314-5822
(toll-free within the United
States and Canada) or
1-408-745-9500 (from outside
the United States).
Input failure to the power
supply
Yellow (minor)Open a support case using the
Case Manager link at
https://www.juniper.net/support/
or call 1-888-314-5822 (toll-free
within the United States and
Canada) or 1-408-745-9500
(from outside the United States).
Power supply drawing
more current than it
should.
Red (major)Open a support case using the
Case Manager link at
https://www.juniper.net/support/
or call 1-888-314-5822 (toll-free
within the United States and
Canada) or 1-408-745-9500
(from outside the United States).
Unrecognized power
supply
Red (major)
130