Function library
Code table
9-257
l
EDSVS9332S-D12 EN 3.0
Code ImportantPossible settings
No. SelectionLenzeLCD
C0034 MST CURRENT 0 0
1
2
-10V...+10V
+4 mA ... +20 mA
-20mA...+20mA
Master reference voltage / current
Selection for setpoint selection
C0037 SET-VALUE RPM 0 -16000 {1 rpm} 16000 Setpoint selection (rpm)
C0039 -199.99 {0.01 %} 199.99
NSET JOG setpoints
1 JOG SET-VALUE 100.00
p
Fixed speeds (JOG setpoints) can be selected
f
o
r
N
S
E
T
u
s
i
n
g
d
i
g
i
t
a
l
i
n
p
u
t
s
2 JOG SET-VALUE 75.00
f
o
r
NSET using digi
t
al inpu
t
s
3 JOG SET-VALUE 50.00
4 JOG SET-VALUE 25.00
5 JOG SET-VALUE 0.00
... ... ...
14 JOG SET-VALUE 0.00
15 JOG SET-VALUE 0.00
C0040 CTRL ENABLE 1 0
1
Controller inhibited
Controller enabled
Controller enable RFR
C0042 QSP 1
2
QSP: Not active
QSP: Active
Quick stop
C0043 TRIP RESET 0 0
1
TRIP RESET
Active error
Error reset
Resetofanactivetrip:
Set C0043 = 0
C0045 ACT JOG 0
1
2
...
15
Nset active
JOG 1
JOG 2
...
JOG 15
NSET
JOG selection
C0046 NSET-N -199.99 {0.01 %} 199.99 NSET
Main setpoint
C0049 NSET-NADD -199.99 {0.01 %} 199.99 NSET
Additional setpoint
C0050 MCTRL-NSET2 -100.00 {0.01 %} 100.00 MCTRL
n
set
at speed controller input
C0051 MCTRL-NACT -30000 {1 rpm} 30000 Actual speed value
C0052 MCTRL-UMOT 0 {1 V} 800 Motor voltage
C0053 UG-VOLTAGE 0 {1 V} 900 DC-bus voltage
C0054 IMOT 0.0 {0.1 A} 500.0 Imot (motor current)
C0056 MCTRL-MSET2 -100.00 {0.01 %} 100.00 MCTRL
Torque setpoint (controller output with torque
precontrol (MCTRL-M-ADD)
C0057 MAX TORQUE 0 {1 Nm} 500 Maximum torque (C0086/C0022)
Maximum possible torque of the drive
configuration
depending on C0022, C0086
C0058 ROTOR DIFF -90.o -180.0 {0.1 °} 179.9 Rotor displacement angle
Zero phase of the rotor for synchronous motors
(C0095)
C0059 MOT POLE NO. 1 {1} 50 Number of motor pole pairs
C0060 ROTOR POS 0 {1} 2048 Motor rotor position
1 rev. = 2048 inc
C0061 HEATSINK TEMP 0 {1 °C} 100 Heatsink temperature
C0063 MOT TEMP 0 {1 °C} 200 Motor temperature
C0064 UTILISATION 0 {1 %} 150 Device load Ixt during the last 180 s
C0064 > 100 % releases OC5
Trip reset is possible only if C0064 < 95 %
C0067 ACT TRIP All fault indications Æ Selection list 10 Error message TRIP