Function library
Code table
9-261
l
EDSVS9332S-D12 EN 3.0
Code ImportantPossible settings
No. SelectionLenzeLCD
C0168 All fault indications List of errors occurred
1 FAIL NO. ACT Currently active fault
2 FAIL NO: OLD1 Last fault
... ... ...
8 FAIL NO: OLD7 Last but six fault
C0169
Corresponding mains switch-on time List of the times when the faults occurred under
C0168 (referring to C0179)
1 FAIL TIME ACT Currently active fault
2 FAILTIME OLD1 Last fault
... ... ...
8 FAILTIME OLD7 Last but six fault
C0170
Corresponding mains switch-on time List which indicates how often the faults have
occurred consecutively under C0168
History buffer
1 COUNTER ACT Currently active fault
2 COUNTER OLD1 Last fault
... .. ...
8 COUNTER OLD7 Last but six fault
C0172 OV REDUCE 0 0 {10 V} 100 OV reduce
Threshold to activate the brake torque reduction
before OU fault
[C0173] UG LIMIT 1
Overvoltage shutdown-threshold (OU)
Check during commissioning and adapt, if
necessary
All drive components in DC bus connections
must have the same thresholds
0 Mains < 400V, ±B
LU = 285 V, OU = 770 ... 755 V
Operationonmains<400Vwithorwithout
brake unit
1 Mains = 400V, ±B
LU = 285 V, OU = 770 ... 755 V
Operation on 400 V mains with or without brake
unit
2 Mains = 460V, ±B
LU = 328 V, OU = 770 ... 755 V
Operation on 460 V mains with or without brake
unit
3 Mains = 480V, B, OU = 770 V
LU = 342 V, OU = 770 ... 755 V
Operation on 480 V mains without brake unit
4 Mains = 480V, B, OU = 800 V
LU = 342 V, OU = 800 ... 785 V
Operation on 480 V mains with brake unit
C0178 OP TIMER 0 {1 s} 4294967295 Elapsed time meter
Time when the controller was enabled
C0179 MAINS TIMER 0 {1 s} 4294967295 Power-on time meter
Time when the mains was switched on
C0182 TI S-SHAPED 20.00 0.01 {0.01 s} 50.00 NSET
T
i
time of the S-shaped ramp function generator
(determines the shape of the S curve)
Small values ⇒small S rounding
Large values ⇒large S rounding