DLP-537: Detailed Level Procedure 363-206-285
Page 4 of 6 Issue 2, February 2000
DDM-2000 OC-3 MULTIPLEXER
20.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lighted. Batteries must not be connected or disconnected
when
TESTING
indicator is lighted.
Ensure that TESTING indicator is not lighted. (READY indicator lighted).
Unplug battery pack and repeat from Step 5.
21.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lighted. Batteries must not be connected or disconnected
when
TESTING
indicator is lighted.
Depress test set START/CONTINUE button.
22. Does test set TESTING indicator light, READY indicator go off, and TIME
display start counting time?
If YES, then proceed to Step 24.
If NO, then continue with Step 23.
23.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lighted. Batteries must not be connected or disconnected
when
TESTING
indicator is lighted.
There is a defective test set. Depress STOP button, unplug battery, and return
test set for repair.
24. Depress test set STOP button.
25. Does test set STOP indicator light and TIME display stop counting time?
If YES, then proceed to Step 27.
If NO, then continue with Step 26.
26.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lighted. Batteries must not be connected or disconnected
when
TESTING
indicator is lighted.
There is a defective test set. Allow test to run for 15 minutes as shown on TIME
display. When COMPLETE indicator lights, unplug battery, and return test set
for repair.