EasyManua.ls Logo

Mitsubishi Electric QJ71GF11-T2 - Page 100

Mitsubishi Electric QJ71GF11-T2
568 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
98
RX/RY Setting
Assign RX/RY points. ( Page 124, Section 8.1.1)
Points can be assigned in increments of 16 (Start: 0
H
, End:
F
H
).
When "Sub-Master Station" is selected in "Station Type", points can
also be assigned for the master station. ( Page 180, Section 8.8)
Points:
Device number: 0 to 3FFF
H
(Default: Blank)
RWw/RWr Setting
Assign RWw/RWr points in increments of 4. ( Page 124, Section
8.1.1)
When "Sub-Master Station" is selected in "Station Type", points can
also be assigned for the master station. ( Page 180, Section 8.8)
Points:
Device number: 0 to 1FFF
H
(Default: Blank)
Refresh Device
Link refresh target devices in the CPU module are displayed for each
link device of the master/local module.
Target devices are displayed when refresh parameters have been set.
( Page 103, Section 7.5)
Reserved/Error Invalid
Station
Set this item to reserve the slave station or to set the slave station as
an error invalid station. ( Page 176, Section 8.5)
This item cannot be set for the submaster station.
•No Setting
The slave station is connected to the network.
Reserved Station
The slave station is reserved for future expansion. By reserving a
slave station, link device assignment will not change even if the
slave station is added or the reservation is cancelled. Therefore, the
program needs not to be modified. Physical connection of the slave
station is not required.
Invalid Station
Even if a slave station is disconnected during data link, the master
station will not detect the slave station as a faulty station.
•No Setting
Reserved Station
Invalid Station
(Default: No Setting)
Alias
Enter the name of a device if required.
The name entered is displayed in "Network Status" of the CC-Link IE
Field diagnostics.
Up to 8 characters
(Default: Blank)
Comment Enter a comment if required.
Up to 32 characters
(Default: Blank)
Item Description Setting range
Station Type
Setting
range
Master Station, Local
Station, Intelligent
Device Station, Sub-
Master Station
16 to 2048
Remote Device Station 16 to 128
Remote I/O Station 16 to 64
Station Type
Setting
range
Master Station, Local
Station, Intelligent
Device Station, Sub-
Master Station
4 to 1024
Remote Device Station 4 to 64
Remote I/O Station
Cannot be
set.

Table of Contents

Related product manuals