540
(c) Parameter set flag (buffer memory address: 31740 (7BFC
H
))
Data stored to this buffer memory indicates completion of parameter setting, sends a cyclic start request, and
stores the results of these two operations.
Also, the buffer memory stores the results of the commands above.
•00
H
: Initial/idle status (stored by the system)
•01
H
: Parameter setting ended (stored by the user)
•02
H
: Parameter communication completed (stored by the system)
•03
H
: Cyclic start being requested (stored by the user)
•FE
H
: Parameter communication failed (stored by the system)
•FF
H
: Cyclic start completed (stored by the system)
(d) Switch setting parameter check result (buffer memory address: 31741 (7BFD
H
))
This buffer memory stores the results of the switch setting parameter check.
• 0: Normal
• 1 or greater: Error (error code)
(e) Parameter communication result (buffer memory address: 31742 (7BFE
H
))
This buffer memory stores the result of parameter communications between the C Controller module and the
master/local module.
• 0: Normal
• 1 or greater: Error (error code)
(f) Setting flag (buffer memory address: 31743 (7BFF
H
))
• For the master station and the submaster station
Use b0 to b2 to set whether to enable each setting data.
Storing "0: Invalid" will operate the station with the default of the parameter. ( Page 81, CHAPTER 7)
Use b3 to set whether to enable the submaster function.
Use b4 and b5 to set whether to enable the IP packet transfer function.
Use b8, b9, and b11 to configure the network operation settings.
Bit Item Setting
b0 Network configuration setting data
0: Invalid
1: Valid
b1 Reserved station specification data
b2 Error invalid station setting data
b3 Submaster function
b4 and b5 IP packet transfer function
b8 Data link faulty station setting
0: Clear
1: Hold
b9 Output setting during CPU STOP
0: Hold
1: Clear
b11 Loopback function setting
0: Not used
1: Used
b7
Fixed to 0
to b3b4b5b6 b2 b1 b0b15 to b11b12 b10 b9 b8
Fixed to 0
b4
0: Disable
1: Enable
Fixed to 0.
b5