544
(6) Debugging
When the master/local module is mounted with a C Controller module, debugging cannot be performed from GX
Works2 by connecting it to the C Controller module.
How to perform debugging varies depending on the C Controller module used.
When the master/local module is mounted with the Universal model QCPU, debugging can be performed by CC-Link IE
Field Network diagnostics from GX Works2 connected to the Universal model QCPU. ( Page 206, CHAPTER 9)
(a) Q06CCPU-V, Q06CCPU-V-B, and Q12DCCPU-V (Basic mode)
Check the LEDs of the C Controller module and master/local module and perform debugging. If an error has
occurred, check the error code and perform debugging.
Checking LEDs
For the LEDs of a C Controller module, refer to the manual for the C Controller module.
For the LEDs of a master/local module, refer to Page 430, Section 12.3. Note that debugging cannot be
performed using GX Works2.
Checking error codes
Check error codes using the C Controller setting utility.
Error codes can be checked in "Error code" under the "Module information" tab.
C Controller setting utility "Module information" tab button