CHAPTER 8 FUNCTIONS
8
8.1 Cyclic Transmission
8.1.7 Input and output status settings in case of failure
(1) Setting method
(a) Input status of data link faulty station
Set this item in the "Network Operation Settings" window. ( Page 101, Section 7.4)
(b) Cyclic data output when a stop error occurs in the CPU module
Select "PLC Parameter" and set it in "Intelligent Function Module Detailed Setting".
[Project Window] [Parameter] [PLC Parameter] "I/O Assignment" tab
button "Error Time Output Mode"
(2) Precautions
(a) When data link is stopped by users
When cyclic transmission is stopped using one of the following methods, the input status of the faulty station is
held.
CC-Link IE Field Network diagnostics ( Page 221, Section 9.4)
Link special relay (SB), link special register (SW) ( Page 408, Section 11.4 (1))
(b) Setting on a station with a data link error
When the following settings are set to "Hold" on the station where a data link error has occurred, the input
status of the own station upon error is held, regardless of setting.
"Network Operating Settings" "Output Setting During CPU STOP" ( Page 141, Section 8.1.7 (2))
"PLC Parameter" "Intelligent Function Module Detailed Setting" "Error Time Output Mode"
( Page 139, Section 8.1.6 (1) (b))