168
(b) Setting in the CPU module 1 and master station 1 (station number 0)
1. Set the routing parameters to the CPU module 1.
Because the network address is different from that of the request destination device, the Ethernet adapter
module 2 (Ethernet part) does not have a network number. Set the communication route to the network
number 2.
Project window [Parameter] [Network Parameter] [Ethernet/CC IE/
MELSECNET] button
2. Set the IP address in the master station 1 (station number 0).
Project window [Parameter] [Network Parameter] [Ethernet/CC IE/
MELSECNET] button
3. Write the set parameters to the CPU module 1. Then reset the CPU module or power off and on the
system.
[Online] [Write to PLC]
or Power OFF ON
RESET