268
*1 If Completion status ((S1)+1) is "Channel in use (dedicated instruction) (error codes: D25A
H
and D25B
H
)", data is not
stored.
(b) Start device of the own station where data to be written is stored
Specify the start device of the own station that stores data to be written.
(S1)+8
Arrival monitoring
time
Specify the monitoring time until instruction completion. (It can be set
when the execution type set by (S1)+0 is "1: With arrival
confirmation".)
If the instruction is not completed within the specified time, the
instruction is resent for the number of resends specified by (S1)+7.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
0 to 32767 User
(S1)+9 Write data length Specify the number of words to be written.
1 to 960
To QnACPU:
1 to 480 words
User
(S1)+10 Unused 0User
(S1)+11 Clock set flag
The valid or invalid status of data after (S1)+12 is stored.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
0: Invalid
1: Valid
System
(S1)+12 to
(S1)+15
Clock data of
abnormal end
Clock data of abnormal end is stored in BCD format.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
When the target station is QnACPU, 00
H
is stored in the year (the
first two digits of the year).
System
(S1)+16
Error-detected
station's network
No.*
1
The network No. of the station in which an error was detected is
stored.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
1 to 239: Network No.
System
(S1)+17
Error-detected
station number*
1
The station number of the station in which an error was detected is
stored.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
Master station: 125 (7D
H
)
Local station, intelligent device station, submaster station: 1 to 120
System
Device Item Setting data Setting range Set by
(S1)+12
(S1)+13
(S1)+14
(S1)+15
Month (01
H to 12H)
Hour (00
H to 23H)
Second (00
H to 59H)
Day (01
H to 31H)
Minute (00
H to 59H)
00
H (Sun.) to 06H (Sat.)
Day of week (00
H
to 06
H
)
Year (00H to 99H), first 2 digits
Year (00
H
to 99
H
), last 2 digits
b15 b8 b7 b0