Mitsubishi Electric QJ71GF11-T2 - Appendix 5.3 Cyclic Transmission Delay Time; Between the Master Station and an Intelligent Device Station;Remote Device Station; Master Station (Rx;Rwr) Intelligent Device Station;Remote Device Station (Input); Master Station (Ry;Rww) Intelligent Device Station;Remote Device Station (Output)

Mitsubishi Electric QJ71GF11-T2
568 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
524
Appendix 5.3 Cyclic transmission delay time
The following is the formula to calculate cyclic transmission delay time.
(1) Between the master station and an intelligent device station/remote device
station
(a) Master station (RX/RWr) Intelligent device station/remote device station (input)
The following time is shown:
The time between a signal input to the intelligent device station/remote device station and the CPU module
device of the master station turning on or off
The time between data input to the intelligent device station/remote device station and the data being
stored in the CPU module device of the master station
SM : Master station sequence scan time
LS : Link scan time
n1 : SM LS (Round up the calculated value to the nearest integer.)
Rio : Intelligent device station/remote device station processing time
( Manual for the intelligent device station/remote device station used)
(b) Master station (RY/RWw) Intelligent device station/remote device station (output)
The following time is shown:
The time between the CPU module device of the master station turning on or off and the output of the
intelligent device station/remote device station being turning on or off
The time between data set to the CPU module device of the master station and the data output to the
intelligent device station/remote device station
SM : Master station sequence scan time
LS : Link scan time
n2 : LS SM (Round up the calculated value to the nearest integer.)
Rio : Intelligent device station/remote device station processing time
( Manual for the intelligent device station/remote device station used)
Calculation
value
Block Data Assurance per Station No Block Data Assurance per Station
Asynchronous mode Synchronous mode Asynchronous mode Synchronous mode
Normal value (SM × 1) + (LS × n1) + Rio (SM × 1) + (LS × 1) + Rio (SM × 1) + (LS × 1) + Rio (SM × 1) + (LS × 1) + Rio
Maximum
value
(SM × 1) + {LS × (n1 + 1)} + Rio (SM × 1) + (LS × 2) + Rio (SM × 1) + (LS × 2) + Rio (SM × 1) + (LS × 2) + Rio
Calculation
value
Block data assurance per station No block data assurance per station
Asynchronous mode Synchronous mode Asynchronous mode Synchronous mode
Normal value (SM × n2) + (LS × 1) + Rio (SM × 1) + (LS × 1) + Rio (SM × 1) + (LS × 1) + Rio (SM × 1) + (LS × 1) + Rio
Maximum
value
(SM × n2) + (LS × 2) + Rio (SM × n2) + (LS × 1) + Rio (SM × 2) + (LS × 2) + Rio (SM × n2) + (LS × 1) + Rio