CHAPTER 7 PARAMETER SETTING
7
7.5 Refresh Parameters
7.5 Refresh Parameters
Set link refresh ranges between the link devices of the master/local module and the devices of the CPU module.
(1) Setting procedure
1. Set network setting parameters. ( Page 84, Section 7.2)
2. Open the setting window.
Project window [Parameter] [Network Parameter] [Ethernet/CC IE/MELSECNET]
button
3. Set parameters in the window.
4. Click the button.
Item Description Setting range
Assignment Method
Select a link device assignment method.
Points/Start: Enter the points and start numbers of link devices.
Start/End: Enter the start and end numbers of link devices.
Points/Start
•Start/End
(Default: Start/End)
Transfer SB
Transfer
SW
Dev. Name
Set the link refresh ranges of SB and SW. One range can be set for
each SB and SW. ( Page 127, Section 8.1.2)
(1) Transfer SB
Link Side: Fixed at "SB".
PLC Side: M, L, B, D, W, R, SB, ZR
(2) Transfer SW
Link Side: Fixed at "SW".
PLC Side: M, L, B, D, W, R, SW, ZR
(Default: Blank)
Points,
Start, End
Link Side: 0 to 1FF
H
PLC Side: Within device range of
CPU module
(Default: Blank)
Set bit devices in increments of 16
points and word devices in increments
of 4 points.
Ex.
0000
H
Device
name
(SB)
Transfer
SB
Transfer
SW
01FFH
Master/local module CPU module
0000H
01FFH
0000H
01FFH
0000H
01FFH
Device
name
(SW)
Device
name
(SB)
Device
name
(SW)