90
(a) Setting the configuration of the slave station in the master station
Item Description Setting range
Mode Setting
Set the mode of the master station. ( Page 84, Section 7.2 (1))
Online (Normal Mode)
Online (High Speed Mode)
•Offline
H/W Test
Self-Loopback Test
Loop Test
(Default: Online (Normal Mode))
Assignment Method
Select a link device assignment method.
Point/Start: Enter the points and start numbers of link devices.
Start/End: Enter the start and end numbers of link devices.
Point/Start
•Start/End
(Default: Start/End)
Link Scan Time
(Approx.)
Displays the approximate link scan time.
No.
The total number of slave stations and submaster stations set in the CC IE
Field configuration window is displayed.
Model Name
The module model name is displayed.
If a module where the profile is not registered is set, the message "Module
without profile" is displayed. Register the profile before setting the model
name.
For how to register a profile, refer to the following.
GX Works2 Version1 Operating Manual (Common)
STA#
Enter the station number of each slave station or the submaster station
connected to the network.
Station numbers do not need to be set consecutively, but must be unique.
The station number of the master station is fixed at "0".
1 to 120
(Default: Blank)
Station Type
Select the station type (excluding the master station). Select the station type
same as that of the modules connected to the network.
Remote I/O Station
Remote Device Station
Intelligent Device Station
Local Station
Sub-Master Station
(Default: varies depending on the set
module)
RX/RY Setting
Assign RX/RY points. ( Page 124, Section 8.1.1)
Points can be assigned in increments of 16 (Start: 0
H
, End: F
H
).
When "Sub-Master Station" is selected in "Station Type", points can also be
assigned for the master station. ( Page 180, Section 8.8)
To equally assign points or the same points, go to [Equal Assignment] or
[Identical Point Assignment] under [CC IE Field Configuration].
( Page 95, Section 7.3 (1) (d))
Points:
Device number: 0 to 3FFF
H
(Default: varies depending on the set
module)
Station Type
Setting
range
Master Station, Local
Station, Intelligent
Device Station, Sub-
Master Station
16 to 2048
Remote Device Station 16 to 128
Remote I/O Station 16 to 64