170
(d) Setting in the Ethernet adapter module 2 (station number 1)
1. Set the IP address to the Ethernet adapter module 2 (Ethernet part).
Use the configuration tool to set the IP address in the Ethernet adapter module 2 (Ethernet part).
Setting item tree NZ2GF-ETB [Parameter] "Ethernet"
2. The IP address setting is not required for the Ethernet adapter module 2 (CC-Link IE Field Network
part).
The network address set in the master station 2 (station number 0) is automatically assigned.
3. The CC-Link IE Field Network gateway setting is not required for the Ethernet adapter module 2.
Because the network address of the request destination (Ethernet adapter module 1) is the same as that
of the master station, setting only the communication route in the routing parameters allows
communications to be performed with the request destination.
4. Write the set parameters to the Ethernet adapter module 2.
[Online] [Write]