CHAPTER 7 PARAMETER SETTING
7
7.7 Interlink Transmission Parameters
(e) Performing interlink transmission in a multiple CPU system
When different control CPUs are set for the network modules, interlink transmission cannot be performed using
interlink transmission parameters or a program. Use the CPU shared memory of the multiple CPU system.
(3) Setting example
The following is a setting example to perform interlink transmission from the master station on CC-Link IE Field
Network to stations on CC-Link IE Controller Network. In this example, 128-point data input from the slave station
(station number 1) is transferred.
1. Select "CC IE Field (Master Station)" for "Transfer From" and "CC IE Control (Normal Station)" for
"Transfer To" and enter the transfer ranges of link devices.
2. Click the button.
128
points
Slave station
(Station No.1)
CC-Link IE
Controller Network
CC-Link IE
Field Network
Master station
(Station No.0)
Normal station
(Station No.4)
Station No.1 send
range
Station No.2 send
range
Station No.3 send
range
Station No.4 send
range
Control station
(Station No.1)
Normal station
(Station No.2)
Normal station
(Station No.3)
Input
RX200
RX LB
RX27F
LB780
LB7FF
Select "CC IE Field (Master Station)" for transfer source, and "CC IE Control
(Normal Station)" for transfer target.
Input the range of Interlink Transmission Parameters.