EasyManua.ls Logo

Mitsubishi Electric QJ71GF11-T2 - Buffer Memory

Mitsubishi Electric QJ71GF11-T2
568 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
537
APPENDICES
A
Appendix 7 Mounting the Master/Local Module with a C Controller Module
Appendix 7.1 Setting the parameters using the buffer memory in the master/local module
(5) Buffer memory
The following table lists the buffer memory areas set by parameters when the master/local module is mounted
with a C Controller module.
When the master/local module is mounted with a programmable controller CPU, the buffer memory areas listed in this
section cannot be used.
For parameter setting when a programmable controller CPU is used, refer to the following.
Page 81, CHAPTER 7, Page 359, Section 10.17
: Can be set,×: Cannot be set
Address
(decimal
(hexadecimal))
Name
Availability
Initial
value
Reading
/writing
Reference
Master
station
Local
station
31740 (7BFC
H
)
Parameter set flag 0
Reading/
writing
Page 540,
Appendix 7
(5) (c)
31741 (7BFD
H
)
Switch setting parameter check result 0
Reading/
writing
Page 540,
Appendix 7
(5) (d)
31742 (7BFE
H
)
Parameter communication result 0
Reading/
writing
Page 540,
Appendix 7
(5) (e)
31743 (7BFF
H
)
Setting flag 0
Reading/
writing
Page 540,
Appendix 7
(5) (f)
31744 (7C00
H
)
Application
parameter
Total number of slave
stations
×0
Reading/
writing
Page 541,
Appendix 7
(5) (g)
31745 to 71757
(7C01
H
to 7C0D
H
)
System area
31758 to 31765
(7C0E
H
to 7C15
H
)
Reserved station
specification
×0
Reading/
writing
Page 542,
Appendix 7
(5) (h)
31766 to 31773
(7C16
H
to 7C1D
H
)
Error invalid station setting × 0
Reading/
writing
Page 542,
Appendix 7
(5) (i)
31774 (7C1E
H
)
Network
configuration
setting data
(1st station)
Slave station setting
information
×
0
Reading/
writing
Page 543,
Appendix 7
(5) (j)
31775 (7C1F
H
)
RX/RY offset ×
31776 (7C20
H
)
RX/RY size ×
31777 (7C21
H
)
RWw/RWr offset ×
31778 (7C22
H
)
RWw/RWr size ×
31779 to 32378
(7C23
H
to 7E7A
H
)
Network
configuration
setting data
(2nd to 121st
stations)
Same as in Network
configuration setting data
(1st station)
×0
Reading/
writing
Page 543,
Appendix 7
(5) (k)
32379 to 32380
(7E7B
H
to 7E7C
H
)
IP address × 0
Reading/
writing
Page 543,
Appendix 7
(5) (l)

Table of Contents