274
(b) Devices used in the program
Link special relay (SB), link special register (SW)
Remark
For details on link special relay (SB) and link special register (SW), refer to the following:
Page 473, Appendix 3, Page 493, Appendix 4
Devices used by the user
(c) WRITE instruction setting
The following table lists values set in WRITE instruction control data.
Device Description Device Description
SB0047 Baton pass status (own station) SW00A0.2
Baton pass status (each station) of station
No.3
Device Description Device Description
M110 Control data setting command M116 Completion status indication device
M111 Write data setting command
D220 to
D237
Control data
M112 Start contact
D750 to
D753
Write data storage device (station No.2)
M115 Completion device
Device Item Set value
(S1)+0 D220 Execution/abnormal end type
0081
H
. (With arrival confirmation, sets data for
abnormal end)
(S1)+1 D221 Completion status
(The system sets this item.)
(S1)+2 D222 Channels used by own station 2
(S1)+3 D223 Target station's CPU type
0000
H
(control CPU)
(S1)+4 D224 Target station's network No. 1
(S1)+5 D225 Target station number 3
(S1)+6 D226 (Unused) 0
(S1)+7 D227 Number of resends 5 times
(S1)+8 D228 Arrival monitoring time 0 (10 seconds)
(S1)+9 D229 Write data length 4 words
(S1)+10 D230 (Unused) 0
(S1)+11 D231 Clock set flag
(The system sets these items.)
(S1)+12 to
(S1)+15
D232 to D235 Clock data of abnormal end
(S1)+16 D236
Error-detected station's
network No.
(S1)+17 D237 Error-detected station number