CHAPTER 10 DEDICATED INSTRUCTIONS
10
10.8 JP/GP.SEND (Sending Data to the Programmable Controller on Another Station)
(4) Program example
The following program is for sending data of D750 to D753 of station No. 0 (own station) to channel 2 of station
No. 2 (target station) when M152 is turned on.
For details on how to read the data, which was sent by the SEND instruction, from channel 2 of station No. 2
(target station), refer to the following.
To read the data in the main routine program: Page 294, Section 10.9
To read the data in an interrupt program: Page 301, Section 10.10
(a) System configuration
(b) Devices used in the program
Link special relay (SB), link special register (SW)
Remark
For details on the link special relay (SB) and link special register (SW), refer to the following:
Page 473, Appendix 3, Page 493, Appendix 4
Devices used by users
Device Description Device Description
SB0047 Baton pass status (own station) SW00A0.1
Baton pass status (each station) of station No.
2
Device Description Device Description
M150 Control data setting command M156 Completion status indication device
M151 Send data setting command
D350 to
D367
Control data
M152 Start contact
D750 to
D753
Send data storage device (station No.0)
M155 Completion device
RECV
Station No.2
Network No.1
Station No.0
Master/local
module
Master/local
module
CPU module CPU module
SEND
Channel 2
Channel 1
Channel 2
Channel 1