378
(c) Devices used in the program
(d) CCPASET instruction setting
Control data
Network configuration setting data
Device Description Device Description
M191 Start contact
D2010 to
D2024
Network configuration setting data
M192 Completion device
D2610 to
D2617
Reserved station specification data
M193 Completion status indication device
D2620 to
D2627
Error invalid station setting data
D2000 to
D2003
Control data -
Device Item Setting value
(S1)+0 D2000 Completion status (The system sets this item.)
(S1)+1 D2001 Setting flag
0109
H
Network configuration settings: Valid
Reserved station specification: Invalid
Error invalid station setting: Invalid
Submaster function: Valid
IP packet transfer function: Disable
Data link faulty station setting: Hold
Output setting during CPU STOP: Hold
Link scan mode setting: Asynchronous
Loopback function setting: Not used
(S1)+2 D2002 Total number of slave stations 3
(S1)+3 D2003 Constant link scan time 0 (No setting)
Device Item Setting value
(S2)+0 D2010
1st station
Slave station setting
information
F100
H
Station type: Master station
Station number: 0
(S2)+1 D2011 RX/RY offset
0
H
(S2)+2 D2012 RX/RY size 32 points
(S2)+3 D2013 RWr/RWw offset
0
H
(S2)+4 D2014 RWr/RWw size 16 points
(S2)+5 D2015
2nd
station
Slave station setting
information
3101
H
Station type: Local station
Station number: 1
(S2)+6 D2016 RX/RY offset
20
H
(S2)+7 D2017 RX/RY size 32 points
(S2)+8 D2018 RWr/RWw offset
10
H
(S2)+9 D2019 RWr/RWw size 16 points
(S2)+10 D2020
3rd station
Slave station setting
information
4102
H
Station type: Submaster station
Station number: 2
(S2)+11 D2021 RX/RY offset
40
H
(S2)+12 D2022 RX/RY size 32 points
(S2)+13 D2023 RWr/RWw offset
20
H
(S2)+14 D2024 RWr/RWw size 16 points