Number Name Description
Availability
Master
station
(submaster
station)
Local
station
SW0000
Link stop/start direction
Sets the station where cyclic transmission is stopped or started.
00
H
: Own station
01
H
: All stations
02
H
: Specified station
80
H
: Own station (Forced link start)
81
H
: All stations (Forced link start)
82
H
: Specified station (Forced link start)
• Stopping/starting of cyclic transmission is performed by System link
start (SB0002) or System link stop (SB0003).
• When Specified station ( 02
H
or 82
H
) is selected, the own station is not
included.
(Master
operating
station only)
×
SW0001
to
SW0008
When setting 02
H
or 82
H
by the Link stop/start direction (SW0000), this
sets the station No. that stops or starts cyclic transmission.
0: No direction issued for stop or start
1: Direction issued for stop or start
• To specify the master station operating as a submaster station (station
number 0), turn on the bit of the station number 125.
• While the submaster station is operating as a master operating station,
setting of the submaster station number is ignored.
(Master
operating
station only)
×
SW0009
Arrival monitoring time
(RIRD/RIWT)
Specify the monitoring time until instruction completion.
If the direction is not completed within the time, it is resent for the
number of resends specified by the Number of resends (RIRD/RIWT)
(SW000B).
0: 10 seconds (default value)
1 to 360: 1 to 360 seconds
If a value outside the above settings is made, operation is performed for
360 seconds.
If the Number of resends (RIRD/RIWT) (SW000B) is set, the time until
the dedicated instruction fails is shown below.
(Number of resends (RIRD/RIWT) + 1) × Arrival monitoring time (RIRD/
RIWT)
SW000B
Number of resends
(RIRD/RIWT)
If the instruction is not completed within the monitoring time specified by
the Arrival monitoring time (RIRD/RIWT) (SW0009), this specifies the
number of times that the instruction is resent.
0: Not resent (default value)
1 to 7: 1 to 7 times
If a value outside the above settings is made, the instruction is resent 7
times.
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120125 119 118 117 116 115 114 113
Each number in the table represents station No.
SW0001
SW0002
SW0003
SW0004
SW0005
SW0006
SW0007
SW0008