496
SW0043 Mode status
Stores the mode of own station.
0: Online (Normal Mode)
(Local station: Online)
1: Online (High Speed Mode)
2: Offline
6: Loop test
7: Self-loopback test
9: Hardware test
SW0044 Submaster station No.
Stores the submaster station number that has been set using a
parameter.
Range: 1 to 120
SW0046 Module type
Stores the own station's hardware status.
SW0047
Baton pass status (own
station)
Stores the baton pass status for the own station (transient transmission
possible).
0: Data link in progress
2: Baton pass in progress
3: Baton pass stopped
4: Test in progress
5: Offline
SW0048
Cause of baton pass
interruption
Stores the cause of interruption in the communication (baton pass) of
own station.
00
H
: At normal communication or power-on
30
H
: Cable disconnection
33
H
: Disconnection or reconnection in progress
40
H: Offline mode
41
H
: Hardware test
42
H
: Self-loopback test
Number Name Description
Availability
Master
station
(submaster
station)
Local
station
b15 b2 b1 b0
Module type
00: Module
01: Board
10: HMI
SW0046
00
to
to