8 Settings via the MICT
Rev. 03/2019 137
Error Description
Speed (x RPM) exceeded
overspeed limit (y RPM) at trigger
signal number.
The speed (x RPM) exceeded overspeed limit (
RPM) at
trigger signal number (see Engine – Pickups on page 96).
The reason for this may also be an interference coupling
on the trigger signal.
Supply voltage failure. Supply voltage failure. Please check the power supply of
the device where applicable.
Temperature of controller board
(x °C) exceeded limit (y °C).
The temperature of controller board (x °
) exceeded limit
(y° C). Ensure that there is sufficient air circulation and/or
cooling.
Temperature of device (x °
)
exceeded error threshold limit
(y °C).
The temperature of the device (x °
) exceeded failure
threshold (y °C). Ensure that there is sufficient air
circulation and/or cooling.
Temperature of device (x °
)
exceeded permanent limit (y °C).
The temperature of the device (x °
) exceeded warning
threshold limit (y °C) for more than two minutes. Ensure
that there is sufficient air circulation and/or cooling.
Temperature of output board (x °
)
exceeded limit (y °C).
The temperature of output board (x °
) exceeded limit
(y °C). Ensure that there is sufficient air circulation and/or
cooling.
Temperature sensor of controller
board failed.
The temperature sensor of controller board failed. Restart
the ignition controller. If the error occurs again after
restarting the device, please contact MOTORTECH.
Temperature sensor of output
board failed.
The temperature sensor of output board failed. Restart
the ignition controller. If the error occurs again after
restarting the device, please contact MOTORTECH.
Trigger period (x, triggers counted
y) is not in acceptable range
compared to previous trigger
period (z).
The trigger period (x, triggers counted
) is not in
acceptable range compared to previous trigger period (z).
Check the pickups and the corresponding configuration
(see Engine – Pickups on page 96). Furthermore, also pay
attention to the instructions in the section entitled Pickup
Input Errors on page 164.
Trigger signal missing. Current
trigger period (triggers counted x)
is out of the specified range
related to the previous trigger
period.
The trigger signal is missing. Current trigger period
(triggers counted x) is out of the specified range
compared to the previous trigger period. Check the
pickups and the corresponding configuration (see Engine
– Pickups on page 96). Furthermore, also pay attention to
the instructions in the section entitled Pickup Input Errors
on page 164.