7 Functions and settings
Maschinenfabrik Reinhausen 2014 133222/08 EN TAPCON® 240
1. > Configuration > Continue > Continue >
Comm. Interface 1 > Press until the desired display appears.
ð SCADA Master Address CIC1.
2. Press to change the first digit.
If you wish to enter a multi-digit sequence, proceed to step 3. If you do not
wish to enter additional digits, proceed to step 7.
3. Press until another digit position appears.
4. Press to highlight a digit position.
ð The required digit is highlighted and can be changed.
5. Press or to change the digit.
6. Repeat steps 3 to 5 until all required digits have been entered.
7. Press .
ð The SCADA master address is set.
Enabling unsolicited messages
When using the control system protocol DNP3, you can release the unsolicit-
ed data transmission through the device with this parameter. Data is trans-
ferred when a corresponding event occurs.
This display is only provided for the following interface protocol:
DNP3
The voltage regulator must be restarted after changing this setting.
To enable unsolicited messages, proceed as follows:
1. > Configuration > Continue > Continue >
Comm. interface 1 > Press until the desired parameter is displayed.
ð Unsolicited messages CIC1.
2. Press or to set the option you want.
3. Press .
ð Unsolicited messages are enabled/blocked.