EasyManua.ls Logo

MR tapcon 240 - Adjustment of desired voltage value dependent on active power

MR tapcon 240
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Functions and settings
Maschinenfabrik Reinhausen 201472 222/08 ENTAPCON® 240
The following requirements must be noted to set delay time T2:
The delay time T2 must be greater than the switching pulse time.
The delay time T2 must be greater than the maximum operating time of
the motor-drive unit.
The delay time T2 must be less than the value set for delay time T1.
To set the delay time T2, proceed as follows:
1. > Parameter > Control parameter > Press until the de-
sired parameter is displayed.
ð Delay time T2.
2. Press to increase the time or to reduce it.
3. Press .
ð The delay time T2 is set.
Activating/deactivating delay time T2
To activate/deactivate delay time T2 , proceed as follows:
1. > Parameter > Control parameter > Press until the
desired parameter is displayed.
ð T2 activation.
2. Press or to activate/deactivate T2.
3. Press .
ð The delay time T2 is activated/deactivated.
Adjustment of desired voltage value dependent on active power
You can use these parameters to set an active power-dependent adjustment
of the desired voltage value. The desired value [ 67] you have set will be
adjusted automatically depending on the active power measured. This func-
tion is used to compensate for a voltage drop during increased load or an in-
crease in voltage due to a decentralized feed-in.
Depending on whether positive or negative active power is measured, the
desired value calculation is based on 2 linear equations (see example in dia-
gram below).
Parameter Function Settings (see dia-
gram below)
U
max
: Maximum desired value Maximum set desired value is activated when
P
max
is exceeded.
103.0 V
U
min
: Minimum desired value Minimum set desired value is activated when
value falls below P
min
.
99.0 V
U
0
: Desired value at 0 active
power
Set desired value is activated when measured
active power is 0 MW.
100.00 V
7.4.6

Table of Contents

Other manuals for MR tapcon 240

Related product manuals