10 Messages
Maschinenfabrik Reinhausen 2014152 222/08 ENTAPCON® 240
Event messages
Event message Cause
Undervoltage Event message appears if value falls below un-
dervoltage limit value.
Overvoltage Event message appears if value exceeds over-
voltage limit value.
Overcurrent Event message appears if value exceeds over-
current limit value.
Parallel operation error Event message appears with the following
causes:
Tap synchronization method
Tap position not the same
No master or more than one master
set
Invalid tap position
Incorrect parallel operation method se-
lected for a device
Circulating reactive current minimization
method
Circulating reactive current limit ex-
ceeded
Incorrect parallel operation method se-
lected for a device
Only one device in active parallel oper-
ation group
Motor protection device Event message appears if motor protective
switch triggers.
Blocking Event message appears if the "Blocking" func-
tion is selected for the customer input and there
is a signal at the customer input
No OLTC position Event message appears if no OLTC position is
detected.
Tap-change detection
error
Event message appears if an on-load tap-
change operation has not been detected cor-
rectly.
Table 44: Event messages